A badly sized control valve either hunts near closed or runs wide open with no control margin. Good sizing starts with the hydraulics of the whole loop.
What Cv means
The flow coefficient Cv is the flow of water in US gallons per minute at 60°F that passes through a valve with a 1 psi pressure drop. For liquids, the basic relation is Q = Cv × √(ΔP / SG). Metric users often use Kv, where Cv ≈ 1.156 Kv.
Allocate pressure drop sensibly
Build the system curve: pump head minus static head, line friction and equipment losses. A common rule is to give the control valve 25–33% of the dynamic system loss at normal flow, or at least 0.7–1 bar, so it has authority to control.
Check minimum, normal and maximum cases
Size at maximum flow and confirm the valve opens roughly 70–80% there and stays above 10–20% at minimum flow.
Choked flow, flashing and cavitation
When the pressure at the vena contracta falls below vapour pressure, bubbles form. If downstream pressure recovers above vapour pressure they collapse (cavitation) and damage trim. ISA 75.01 uses the liquid pressure recovery factor FL to predict choked flow.
Characteristic
Equal-percentage trims suit most process loops where valve ΔP falls as flow rises. Linear trims suit loops where ΔP stays nearly constant.