The P&ID is the master document for a process plant. Errors left in it flow into piping, instrumentation, procurement and construction. Here is a condensed checklist we teach in our P&ID review training.
General
- Title block, revision and hold list are correct.
- Legend sheets match the project symbols.
- Every line has a complete line number with size, service, sequence, class and insulation.
- Specification breaks are shown wherever the piping class changes.
- Flow arrows and continuation flags point to the right sheet and line.
Equipment
- Equipment tag, design pressure and temperature are shown.
- Nozzles match the vendor or equipment datasheet.
- Pumps have suction strainers, discharge check valves and minimum-flow protection where needed.
- Vessels have vents, drains, level instruments and PSVs.
- Exchangers have isolation and bypass according to philosophy.
Instrumentation and safety
- Instrument tags follow ISA 5.1 and the project tagging procedure.
- Control valves have isolation and bypass valves where the philosophy requires.
- Fail positions (FO/FC/FL) are marked.
- Interlocks and ESD actions match the cause & effect chart.
- PSV set pressures, sizes and inlet/outlet isolation (locked open) are shown.
Operability
- High-point vents and low-point drains are provided for hydrotest and operation.
- Sample points are accessible and correctly specified.
- Utility connections and double block-and-bleed are shown for hazardous services.
- Slopes, no-pocket and gravity-flow notes are included.
- HAZOP actions are closed and reflected on the drawing.